How many amps can 2.5 mm² wire carry? Wire and cable ampacity table
Short answer
A 2.5 mm² PVC copper wire carries 24 A in conduit on a wall (method B1) and 27 A clipped direct (method C) at 30 °C, per SBC 401 and IEC 60364-5-52. At 45 °C the in-conduit rating drops to about 19 A, so it is protected at 16 A. Under the same reference conditions 4 mm² carries 32 A and 6 mm² carries 41 A.
Why there is no single number per wire
People ask “how many amps does 2.5 carry?” expecting one number. In fact a wire carries the current that keeps its insulation below its limit, 70 °C for PVC. The more the wire is enclosed in an insulated wall, bunched with others in one conduit, or sitting in hot air, the lower the permitted current. So the code gives a table per installation method, then correction factors for temperature and grouping.
The tables below are from SBC 401 (2007 edition), which reproduces IEC 60364-5-52. The current SBC 401-CR-2024 keeps the same structure: Annex B.52 for current-carrying capacities and Annex G.52 for voltage drop. Before final approval, check the official code and your project specification.
Ampacity table for PVC copper wires and cables
| Size (mm²) | A1 · 2 loaded | B1 · 2 loaded | B1 · 3 loaded | B2 · 2 loaded | C · 2 loaded | C · 3 loaded |
|---|---|---|---|---|---|---|
| 1.5 | 14.5 | 17.5 | 15.5 | 16.5 | 19.5 | 17.5 |
| 2.5 | 19.5 | 24 | 21 | 23 | 27 | 24 |
| 4 | 26 | 32 | 28 | 30 | 36 | 32 |
| 6 | 34 | 41 | 36 | 38 | 46 | 41 |
| 10 | 46 | 57 | 50 | 52 | 63 | 57 |
| 16 | 61 | 76 | 68 | 69 | 85 | 76 |
| 25 | 80 | 101 | 89 | 90 | 112 | 96 |
| 35 | 99 | 125 | 110 | 111 | 138 | 119 |
Source: SBC 401 (2007 edition) Tables A.52-2 and A.52-4, the same values as IEC 60364-5-52. A1: single insulated conductors in conduit in a thermally insulated wall. B1: single insulated conductors in conduit on or in a wall. B2: multi-core cable in conduit. C: cable clipped direct to a wall. “2 loaded” = single-phase circuit, “3 loaded” = balanced three-phase circuit.
How to read it: pick the installation method first, then the number of loaded conductors (two for single-phase, three for three-phase; the earth conductor does not count), then read the value. For example 4 mm² in conduit on a wall, single-phase: 32 A at 30 °C.
Temperature correction: 30 °C tables are not enough in Saudi Arabia
The table assumes 30 °C ambient air. Even the Saudi Electricity Company’s planning standard rates its overhead lines at 50 °C air. If a cable runs on a roof, in a service corridor or near outdoor units, take the design ambient set by the consultant and multiply by the factor:
| Ambient (°C) | PVC insulation | XLPE / EPR insulation |
|---|---|---|
| 30 | 1.00 | 1.00 |
| 35 | 0.94 | 0.96 |
| 40 | 0.87 | 0.91 |
| 45 | 0.79 | 0.87 |
| 50 | 0.71 | 0.82 |
| 55 | 0.61 | 0.76 |
Source: SBC 401 (2007 edition) Table A.52-14, identical to the IEC 60364-5-52 table.
| Size (mm²) | 30 °C | 40 °C | 45 °C | 50 °C |
|---|---|---|---|---|
| 1.5 | 17.5 | 15.2 | 13.8 | 12.4 |
| 2.5 | 24 | 20.9 | 19.0 | 17.0 |
| 4 | 32 | 27.8 | 25.3 | 22.7 |
| 6 | 41 | 35.7 | 32.4 | 29.1 |
| 10 | 57 | 49.6 | 45.0 | 40.5 |
| 16 | 76 | 66.1 | 60.0 | 54.0 |
| 25 | 101 | 87.9 | 79.8 | 71.7 |
| 35 | 125 | 108.8 | 98.8 | 88.8 |
Calculation: B1 two-loaded column of Table A.52-2 × PVC factor from Table A.52-14.
More than one circuit in one conduit
Bunched circuits heat one another. Grouping factors for circuits bunched in conduit, trunking or on a surface (Table A.52-17): two 0.80, three 0.70, four 0.65, five 0.60, six 0.57. Multiply them with the temperature factor.
Example: three 2.5 mm² circuits in one conduit at 45 °C: 24 × 0.79 × 0.70 = 13.3 A. A 16 A breaker no longer fits; use 13 or 10 A, split the circuits into separate conduits, or go up to 4 mm² (32 × 0.79 × 0.70 = 17.7 A) to keep 16 A.
From ampacity to breaker
SBC 401 (clause 43-3.2) requires the breaker rating to sit between the load current and the corrected cable capacity, and the conventional tripping current I2 to be no more than 1.45 × Iz. Miniature breakers to IEC 60898-1 trip by 1.45 × In, so with them In ≤ Iz is enough.
- 2.5 mm² in conduit at 45 °C (19.0 A): largest standard breaker 16 A.
- 4 mm² (25.3 A): up to 25 A.
- 6 mm² (32.4 A): up to 32 A.
- 10 mm² (45.0 A): up to 40 A.
- 16 mm² (60.0 A): up to 50 A.
These are for one circuit per conduit; with grouping or higher temperatures, recalculate.
What about XLPE cables?
XLPE insulation runs at 90 °C conductor temperature, so its ratings are higher than PVC and less sensitive to heat (factor 0.82 at 50 °C against 0.71 for PVC). In method C with two loaded conductors, 2.5 mm² XLPE carries 33 A against 27 A for PVC. Do not mix tables: read the one for the actual insulation, and make sure equipment terminals are rated for that temperature.
Aluminium compared with copper
| Size (mm²) | Copper | Aluminium |
|---|---|---|
| 16 | 85 | 66 |
| 25 | 112 | 83 |
| 35 | 138 | 103 |
| 50 | 168 | 125 |
Source: SBC 401 (2007) Table A.52-2.
Aluminium carries roughly three-quarters of what copper carries at the same size, so it usually needs one size larger for the same breaker, plus terminations tested and approved for aluminium as the code requires (Table 52-5). It is therefore a designer’s option for large mains, while final circuits in buildings are normally copper.
Common mistakes when reading ampacity tables
- Reading method C for wires in conduit: C is for cables clipped direct and rates higher than B1; single wires in conduit are read from B1.
- Counting earth and neutral as loaded: a single-phase circuit has two loaded conductors (line and neutral), a balanced three-phase circuit three, and the earth never counts. Where harmonics are high on a three-phase circuit, the designer treats the neutral per the code’s harmonics annex.
- Forgetting grouping: three circuits in one conduit cut the rating to 70 %.
- Mixing PVC and XLPE tables: each insulation has its own table and temperature factor.
- Trusting the number on the coil box: a marketing figure states neither installation method nor temperature; use the code table or the manufacturer’s table with its stated conditions.
- Ignoring hot sections of the route: if the cable crosses an exposed roof or passes a heat source, size on the worst section.
Safety note: this guide is engineering background, not a substitute for the project electrical engineer’s design or the consultant’s approval. Installation and termination must be done by a licensed electrician; isolate the supply at source and prove it dead with a tester before any work.
From calculation to supply
Done with the numbers? Send us the list
Send the sizes and quantities, or the full BOQ, on WhatsApp at +966 55 573 8438; our team checks the specification and replies. We reply to quote requests the same working day.
Frequently asked questions
How many amps does 2.5 mm² wire carry?
PVC copper at 30 °C: 24 A in conduit on a wall, 27 A clipped direct, 19.5 A in conduit in an insulated wall. In conduit at 45 °C about 19 A, so it is protected at 16 A.
How much do 4 mm² and 6 mm² carry?
In conduit, single-phase, at 30 °C: 4 mm² carries 32 A and 6 mm² carries 41 A. At 45 °C about 25.3 A and 32.4 A, i.e. 25 A and 32 A breakers respectively.
How many amps for 10 mm² and 16 mm²?
In conduit, single-phase, at 30 °C: 10 mm² carries 57 A and 16 mm² 76 A. On a three-phase circuit in the same method: 50 A and 68 A. Then apply temperature and grouping factors.
Is 1.5 mm² suitable for socket circuits?
1.5 mm² is the smallest size the code allows for power and lighting, rated 17.5 A in conduit at 30 °C and 13.8 A at 45 °C. It normally serves lighting on a 10 A breaker; socket circuits are set by the project designer from the breaker and load.
References
We checked these sources on the last-updated date. Where the code leaves room for engineering judgement, the decision rests with the project engineer or consultant.
- SBC 401-CR-2024, The Saudi Electrical Code — table of contents (Saudi Building Code National Committee)
- SBC 401-2007 Electrical Requirements, full text (copy hosted by FKEC): §31-1, §41-2.5, §43-3.2, §52-5, Tables 52-5, 54-3, A.52-2, A.52-4, A.52-14, A.52-17
- IEC 60364-5-52:2009 Low-voltage electrical installations — Wiring systems (IEC Webstore)
- ABB SACE, Electrical Installation Handbook Vol. 2 — §2.2 current-carrying capacity (Table 8) and §2.2.2 voltage drop (Tables 1 and 3)
- IEC 60898-1:2015+AMD1:2019 Circuit-breakers for overcurrent protection for household and similar installations (IEC Webstore)
- Saudi Electricity Company, Distribution Planning Standard DPS (March 2004) — §1.4 frequency, Table 1.2 service voltages, Table 3.2 demand factors (third-party copy)
- Saudi Cable Company, Building Wires catalogue — 450/750 V PVC wires, conductor DC resistance at 20 °C
More guides
- Air-conditioner cable size: how many mm² do you need? How to size cables for split and central AC units in Saudi Arabia: start from the nameplate current, match the breaker, derate for heat, check voltage drop. Read the guide
- What size breaker for an AC unit, and why does it keep tripping? How to size an AC breaker from the nameplate and cable, B vs C vs D curves, RCD points, and the usual reasons an AC breaker keeps tripping. Read the guide
- Electrical load calculation under the Saudi code SBC 401 Electrical load calculation for a villa or apartment under SBC 401: load schedule, demand factors, phase balance, main breaker and cable, worked example. Read the guide