Technical guide · 5 min read
Air-conditioner cable size: how many mm² do you need?
Short answer
AC cable size follows the current on the unit’s nameplate and its breaker, not the BTU rating alone. For PVC copper wires in conduit, derated to 45 °C, a single-phase circuit needs 2.5 mm² on a 16 A breaker, 4 mm² on 20 or 25 A, and 6 mm² on 32 A. On long runs check the voltage drop, which may call for the next size up.
The question every site asks
“How many mm² does this AC need?” is a question we hear every day from contractors and technicians. The right answer starts with a small label on the outdoor unit: the nameplate. This guide walks you from the unit’s current to the breaker, then to the cable size after correcting for our ambient temperature, and finally to the run length.
The figures come from the tables of the Saudi Electrical Code SBC 401, which is built on IEC 60364; the sources are listed at the end. The final decision still belongs to the project electrical engineer or consultant, because installation method and room temperature differ between projects.
Start from the nameplate, not the tonnage
One ton of refrigeration is 12,000 BTU/h, about 3.517 kW of cooling capacity. That is not the electricity the unit draws; the electrical input is lower and depends on efficiency, which the Saudi standard SASO 2663 for small units now rates by seasonal efficiency (SEER). Two units of the same tonnage can draw noticeably different currents.
Read three things from the nameplate:
- Phases, voltage and frequency, e.g. 220–240 V, 1 Ph, 60 Hz or 380–415 V, 3 Ph, 60 Hz.
- Rated or running current in amperes.
- Central and package units usually add two more: minimum circuit ampacity (MCA) and maximum breaker or fuse (MOCP / Max fuse). When they are given, they are the manufacturer’s binding figures: the cable must not be below the first, and the breaker must not exceed the second.
Single-phase or three-phase, and what voltage in Saudi Arabia?
Council of Ministers Resolution 425 (20/9/1431 H) changes residential and commercial supply from 127/220 V to 230/400 V. SASO notes that 127 V is still found in parts of the Kingdom and is being phased out under the Saudi Electricity Company’s supervision. SEC’s Distribution Planning Standard (2004 edition) sets the nominal frequency at 60 Hz and lists low-voltage service voltages of 220/127 V and 380/220 V at ±5 %. In practice: confirm the voltage at your meter before you calculate.
If you are given power rather than current:
- Single-phase: I = P ÷ (V × cos φ)
- Three-phase: I = P ÷ (√3 × V × cos φ), with V the line-to-line voltage.
A three-phase unit spreads its load over three conductors, so the phase current is lower and the cable can be smaller for the same power.
AC cable size by breaker rating
The core rule in the code (SBC 401 clause 43-3.2) is: design current ≤ breaker rating ≤ corrected cable capacity (Ib ≤ In ≤ Iz). The table applies it to single-core PVC copper wires in conduit (method B1), with the code values multiplied by the 45 °C factor of 0.79:
| Breaker (A) | Single-phase: size | Capacity at 45 °C | Three-phase: size | Capacity at 45 °C |
|---|---|---|---|---|
| 16 | 2.5 mm² | 19.0 A | 2.5 mm² | 16.6 A |
| 20 | 4 mm² | 25.3 A | 4 mm² | 22.1 A |
| 25 | 4 mm² | 25.3 A | 6 mm² | 28.4 A |
| 32 | 6 mm² | 32.4 A | 10 mm² | 39.5 A |
| 40 | 10 mm² | 45.0 A | 16 mm² | 53.7 A |
| 50 | 16 mm² | 60.0 A | 16 mm² | 53.7 A |
| 63 | 25 mm² | 79.8 A | 25 mm² | 70.3 A |
Calculation: method B1 values from Tables A.52-2 (2 loaded) and A.52-4 (3 loaded) × 0.79. At 50 °C use 0.71 instead; 4 mm² single-phase then drops to 22.7 A and no longer suits a 25 A breaker. If several circuits share one conduit, also apply the grouping factor.
For these sizes the protective (earth) conductor equals the phase size up to 16 mm² (code Table 54-3), and each AC unit gets its own circuit and breaker in the panel.
How many AC units can a 16 mm² cable feed?
The right question is: what current can 16 mm² carry in your site conditions, and what is the total AC current on each phase? From the table above, 16 mm² single-core wires in conduit on a three-phase circuit carry about 53.7 A at 45 °C, so the sub-main is protected at 50 A. A multi-core 16 mm² cable in conduit (B2) is rated 62 A at 30 °C, about 49 A at 45 °C, which means a 40 A breaker.
Illustrative example (the current is assumed; use the figure on your units’ nameplates): if each single-phase AC draws 10 A and the three-phase sub-main has a 50 A breaker, four units per phase make 40 A and leave a margin, so 12 units spread evenly over three phases, each with its own breaker in a sub-panel. Do not load a phase right up to the breaker rating, and check voltage drop if the sub-panel is far away.
Run length and voltage drop
A long cable drops voltage at the unit, and a compressor struggles on low voltage. SBC 401 (2007 edition, clause 52-5) recommends no more than 4 % drop between the origin of the installation and the equipment, and the IEC guidance value for non-lighting loads on a public supply is 5 %. The calculation is simple:
ΔV = (V/A/km) × I × L(km)
Example: a single-phase unit at 230 V on a 16 A breaker, 2.5 mm² single-core wires, 40 m: 17.82 × 16 × 0.040 = 11.4 V, i.e. 4.96 %, above 4 %. With 4 mm²: 11.14 × 16 × 0.040 = 7.1 V, only 3.1 %. So 2.5 mm² is fine at 25 m, but at 40 m choose 4 mm². The specific values are in the voltage-drop table of our cable sizing guide.
Copper or aluminium?
Aluminium is lighter and cheaper but carries less current for the same size: in method C with two loaded conductors, 16 mm² aluminium is rated about 66 A against 85 A for copper (Table A.52-2). The code also requires terminations used with aluminium to be tested and approved for that use. For AC final circuits we recommend copper; aluminium is an option the designer may study for large mains.
Safety note: this guide is engineering background, not a substitute for the project electrical engineer’s design or the consultant’s approval. Installation and termination must be done by a licensed electrician; isolate the supply at source and prove it dead with a tester before any work.
From calculation to supply
Done with the numbers? Send us the list
Send the sizes and quantities, or the full BOQ, on WhatsApp at +966 55 573 8438; our team checks the specification and replies. We reply to quote requests the same working day.
Frequently asked questions
What wire size for an 18,000 BTU split AC?
BTU alone does not fix the size. Read the current and maximum breaker from the nameplate: on a 16 A breaker, 2.5 mm² copper in conduit is enough up to 50 °C for short runs; on 20 or 25 A use 4 mm², then check voltage drop on long runs.
How many AC units can a 16 mm² cable run?
A 16 mm² copper cable in conduit on a three-phase circuit carries about 49–54 A at 45 °C depending on type, so it takes a 40 or 50 A breaker. The number of units is whatever keeps the total current per phase below that breaker with a margin, each unit on its own breaker.
Can I use the 30 °C cable tables as they are?
The code tables assume 30 °C air, and Saudi summers are hotter, especially on roofs and in service corridors. Multiply by the temperature factor (0.87 at 40 °C, 0.79 at 45 °C, 0.71 at 50 °C for PVC) or follow the design ambient in the project specification.
What cable does a central or package unit need?
Central units are often three-phase, and their nameplates usually give minimum circuit ampacity (MCA) and maximum breaker (MOCP). Choose a cable whose corrected capacity is not below MCA and a breaker not above MOCP, and leave the final check to the project engineer.
References
We checked these sources on the last-updated date. Where the code leaves room for engineering judgement, the decision rests with the project engineer or consultant.
- SBC 401-CR-2024, The Saudi Electrical Code — table of contents (Saudi Building Code National Committee)
- SBC 401-2007 Electrical Requirements, full text (copy hosted by FKEC): §31-1, §41-2.5, §43-3.2, §52-5, Tables 52-5, 54-3, A.52-2, A.52-4, A.52-14, A.52-17
- IEC 60364-5-52:2009 Low-voltage electrical installations — Wiring systems (IEC Webstore)
- ABB SACE, Electrical Installation Handbook Vol. 2 — §2.2 current-carrying capacity (Table 8) and §2.2.2 voltage drop (Tables 1 and 3)
- Schneider Electric, Electrical Installation Guide — Maximum voltage drop limit (IEC 60364-5-52 Table G.52.1)
- SASO — Saudi standards for plugs and socket-outlets and the 127/220 V to 230/400 V change (Council of Ministers Resolution 425)
- Saudi Electricity Company, Distribution Planning Standard DPS (March 2004) — §1.4 frequency, Table 1.2 service voltages, Table 3.2 demand factors (third-party copy)
- Ton of refrigeration — 12,000 BTU/h ≈ 3.517 kW
- Intertek — SASO 2663/2021 energy-efficiency standard for low-capacity (window and split) air conditioners
More guides
- How many amps can 2.5 mm² wire carry? Wire and cable ampacity table Ampacity of copper wires 1.5–35 mm² by installation method per SBC 401 and IEC 60364-5-52, with Saudi heat and grouping factors, for 2.5, 4 and 6 mm². Read the guide
- What size breaker for an AC unit, and why does it keep tripping? How to size an AC breaker from the nameplate and cable, B vs C vs D curves, RCD points, and the usual reasons an AC breaker keeps tripping. Read the guide
- Electrical load calculation under the Saudi code SBC 401 Electrical load calculation for a villa or apartment under SBC 401: load schedule, demand factors, phase balance, main breaker and cable, worked example. Read the guide