Technical guide · 5 min read
Choosing the right cable size: current, voltage drop and installation method
Short answer
Size a cable in three checks: current, so that the cable rating after temperature and grouping correction is at least the breaker rating; voltage drop, using ΔV = (V/A/km) × current × length, kept within the 4 % SBC 401 recommends from origin to equipment; and short-circuit withstand until the breaker clears. The final size is the largest of the three results.
Three checks, and the size is the largest result
Many sites pick cables “by habit”: 4 mm² for the AC, 16 for the board… and it works until a run gets long or a conduit fills up with circuits. This guide lays out the method a design engineer uses, with figures and sources, so you can check your choice before ordering.
The Saudi code SBC 401 is built on IEC 60364: ampacity tables sit in Annex B.52, voltage drop in clause 52-5 and Annex G.52. Follow the steps in order, then take the largest size any check produces.
Step 1: design current and breaker
Work out the load current Ib: single-phase I = P ÷ (V × cos φ), three-phase I = P ÷ (√3 × V × cos φ). SEC’s planning standard requires customers to keep a power factor of at least 0.85 lagging at the interface. Then choose the breaker In ≥ Ib from the standard series (10, 16, 20, 25, 32, 40, 50, 63 A…).
Step 2: installation method
| Method | Description |
|---|---|
| A1 | Single insulated conductors in conduit in a thermally insulated wall |
| A2 | Multi-core cable in conduit in a thermally insulated wall |
| B1 | Single insulated conductors in conduit on a wall or in masonry |
| B2 | Multi-core cable in conduit on a wall or in masonry |
| C | Cable clipped direct to a wall or embedded direct in masonry |
| D | Cable in conduit or ducting in the ground |
| E | Multi-core cable in free air, e.g. perforated tray |
Source: SBC 401 (2007) Table A.52-1 and the installation-method table in the ABB handbook.
If the method changes along the route (say conduit, then tray, then an insulated wall), size on the worst section. Note that buried cables are referenced to 20 °C soil, while SEC’s standard rates its own buried cables at 35 °C ground temperature; do not use method D values without the ground-temperature correction.
Step 3: temperature and grouping correction
Iz = I0 × k1 × k2, where I0 is the code table value at 30 °C, k1 the temperature factor (PVC: 0.87 at 40 °C, 0.79 at 45 °C, 0.71 at 50 °C) and k2 the grouping factor (two circuits 0.80, three 0.70, four 0.65). The condition is Iz ≥ In. Full tables are in our guide “How many amps can 2.5 mm² wire carry?”.
A note on catalogues: some building wires on the Saudi market use 90 °C-rated PVC rather than 70 °C, as in the Saudi Cable Company catalogue. In that case use the manufacturer’s tables for the actual insulation, and check that equipment terminals are rated for the same temperature.
Step 4: voltage drop
The working formula:
ΔV = (V/A/km) × Ib × L(km) → ΔV% = ΔV ÷ U × 100
with the specific value from the table below and U = 230 V single-phase or 400 V three-phase. SBC 401 (2007 edition, clause 52-5) recommends no more than 4 % from the origin of the installation to the equipment, and IEC Table G.52.1 gives 3 % for lighting and 5 % for other uses on installations supplied from the public network. Follow your project specification.
| Size (mm²) | Single-core · single-phase | Single-core · three-phase | Two-core · single-phase | Three-core · three-phase |
|---|---|---|---|---|
| 1.5 | 29.60 | 25.63 | 30.20 | 26.15 |
| 2.5 | 17.82 | 15.43 | 18.16 | 15.73 |
| 4 | 11.14 | 9.65 | 11.36 | 9.84 |
| 6 | 7.42 | 6.43 | 7.56 | 6.55 |
| 10 | 4.48 | 3.88 | 4.54 | 3.93 |
| 16 | 2.82 | 2.44 | 2.86 | 2.48 |
| 25 | 1.78 | 1.54 | 1.81 | 1.57 |
| 35 | 1.28 | 1.11 | 1.31 | 1.13 |
Source: ABB Electrical Installation Handbook Vol. 2, §2.2.2 Table 3. The same number reads as mV per A per metre. For loads below unity power factor the handbook adds the reactance term, which is small for small sizes.
Worked example: a three-phase sub-board at 400 V, design current 30 A on a 32 A breaker, 60 m away, four-core PVC copper cable in conduit (B2) at 45 °C.
- Current: 6 mm² = 34 × 0.79 = 26.9 A, below 32, fails. 10 mm² = 46 × 0.79 = 36.3 A, passes.
- Voltage drop on 10 mm²: 3.93 × 30 × 0.060 = 7.1 V, i.e. 1.77 %, acceptable with margin for final circuits.
- For comparison, if 6 mm² had passed on current: 6.55 × 30 × 0.060 = 11.8 V, i.e. 2.95 %, using up most of the 4 % before the final circuits.
Result: 10 mm². At 120 m the 10 mm² drop would be about 3.5 %, and the size goes up to 16 mm² (2.48 × 30 × 0.120 = 8.9 V, i.e. 2.2 %).
Step 5: short-circuit withstand
On a short circuit the breaker must clear before the conductor exceeds its insulation limit. The adiabatic check is k² × S² ≥ I² × t, with k = 115 for PVC-insulated copper up to 300 mm² (115 A/mm² for one second from 70 to 160 °C). A 2.5 mm² wire withstands 115² × 2.5² ≈ 82,700 A²s; compare that with the let-through I²t the breaker manufacturer publishes at your prospective fault current. On large feeders and time-delayed breakers this check becomes decisive.
Step 6: earth conductor size
| Line conductor S (mm²) | Protective conductor (mm²) |
|---|---|
| S ≤ 16 | S |
| 16 < S ≤ 35 | 16 |
| S > 35 | S ÷ 2 |
Source: SBC 401 (2007) Table 54-3. The size may also be calculated with the adiabatic equation.
From calculation to order: Riyadh Cables and Bahra
Once you have the size, order with a complete specification: cross-section and cores (e.g. 4×10 mm²), conductor material, insulation and sheath, armour if any, voltage grade (450/750 V for building wires, 0.6/1 kV for LV power cables), reference standard and required length. Konoz is an authorised distributor for Riyadh Cables, MESC and Bahra Cables, supplying every region of the Kingdom from Makkah; send the specification and we match it against the manufacturers’ catalogues rather than guessing a part number.
Safety note: this guide is engineering background, not a substitute for the project electrical engineer’s design or the consultant’s approval. Installation and termination must be done by a licensed electrician; isolate the supply at source and prove it dead with a tester before any work.
From calculation to supply
Done with the numbers? Send us the list
Send the sizes and quantities, or the full BOQ, on WhatsApp at +966 55 573 8438; our team checks the specification and replies. We reply to quote requests the same working day.
Frequently asked questions
What is the cable voltage-drop formula?
Voltage drop (V) = specific value (V per A per km) × current × length in km. For a four-core 10 mm² cable carrying 30 A over 60 m: 3.93 × 30 × 0.06 = 7.1 V, i.e. 1.77 % of 400 V.
What voltage drop is allowed in Saudi Arabia?
SBC 401 (2007, clause 52-5) recommends no more than 4 % of nominal voltage between the origin and the equipment; IEC gives 3 % for lighting and 5 % for other uses on public-supply installations. Project specifications may be stricter.
Do I size the cable on load current or breaker rating?
On the breaker: the corrected cable rating must be at least the breaker rating, and the breaker at least the load current. Voltage drop, however, is calculated on the actual load current.
What is the difference between methods B1, B2 and C?
B1 is single-core wires in conduit, B2 a multi-core cable in conduit, C a cable clipped direct to a wall. C cools best so it rates highest; 2.5 mm² single-phase is 24 A in B1, 23 A in B2 and 27 A in C at 30 °C.
References
We checked these sources on the last-updated date. Where the code leaves room for engineering judgement, the decision rests with the project engineer or consultant.
- SBC 401-CR-2024, The Saudi Electrical Code — table of contents (Saudi Building Code National Committee)
- SBC 401-2007 Electrical Requirements, full text (copy hosted by FKEC): §31-1, §41-2.5, §43-3.2, §52-5, Tables 52-5, 54-3, A.52-2, A.52-4, A.52-14, A.52-17
- IEC 60364-5-52:2009 Low-voltage electrical installations — Wiring systems (IEC Webstore)
- ABB SACE, Electrical Installation Handbook Vol. 2 — §2.2 current-carrying capacity (Table 8) and §2.2.2 voltage drop (Tables 1 and 3)
- Schneider Electric, Electrical Installation Guide — Maximum voltage drop limit (IEC 60364-5-52 Table G.52.1)
- Saudi Electricity Company, Distribution Planning Standard DPS (March 2004) — §1.4 frequency, Table 1.2 service voltages, Table 3.2 demand factors (third-party copy)
- Bayka TD04 — PVC LV cables per HD 603 S1: short-circuit current density 115 A/mm² for 1 s (copper, 70 → 160 °C)
- Saudi Cable Company, Building Wires catalogue — 450/750 V PVC wires, conductor DC resistance at 20 °C
- Riyadh Cables Group — manufacturer website
- Bahra Cables Company — manufacturer website
More guides
- Air-conditioner cable size: how many mm² do you need? How to size cables for split and central AC units in Saudi Arabia: start from the nameplate current, match the breaker, derate for heat, check voltage drop. Read the guide
- How many amps can 2.5 mm² wire carry? Wire and cable ampacity table Ampacity of copper wires 1.5–35 mm² by installation method per SBC 401 and IEC 60364-5-52, with Saudi heat and grouping factors, for 2.5, 4 and 6 mm². Read the guide
- What size breaker for an AC unit, and why does it keep tripping? How to size an AC breaker from the nameplate and cable, B vs C vs D curves, RCD points, and the usual reasons an AC breaker keeps tripping. Read the guide